Getty Images Two fire fighters wearing breathing apparatus are on board a platform which has lifted them above the electrical substation which caught fire in March. One is holding a hose which is dampening down the flames. Smoke is billowing.Getty Images

A report into a fireplace at an electrical energy substation that resulted in Heathrow Airport shutting down for practically a day, inflicting chaos for greater than 200,000 passengers, has been launched.

The National Energy System Operator (NESO) recognized the doubtless reason for the hearth, and mentioned that National Grid which operates the substation was warned a couple of fault seven years in the past.

Here are 5 key findings from the report.

1. The fireplace was brought on by moisture

The NESO report answered one of many key questions – what brought about the hearth?

The gadget which caught fireplace was a “supergrid transformer”, which takes excessive voltage electrical energy from the transmission grid and reduces it to a decrease voltage for the following stage of its path to Heathrow Airport and surrounding homes.

Inspectors mentioned the doubtless trigger was moisture stepping into the high-voltage “bushing” – insulation across the connections.

That brought about a short-circuit and “arcing” – electrical sparks like these in a spark plug – which resulted in a “catastrophic failure”.

That brought about the oil which is used to chill the transformer to catch fireplace, and took two transformers offline, reducing energy to Heathrow.

2. National Grid knew about the issue seven years earlier than the hearth

The report mentioned indicators of moisture had been detected at North Hyde in July 2018.

National Grid’s steerage mentioned these had been “an imminent fault” that ought to be changed.

But the problem wasn’t fastened on the time.

In 2022, primary upkeep on the transformer was deferred.

Multiple additional makes an attempt had been made to schedule upkeep, however none went forward.

3. Heathrow knew an issue with certainly one of its three grid connections would shut the airport

Heathrow makes use of as a lot electrical energy as a small metropolis, and it has three connections to the nationwide grid.

But it new that if certainly one of them went down, it must shut the airport for 10 to 12 hours whereas key techniques had been related to the opposite sources of provide.

It didn’t assume it was a possible state of affairs, so it was not thought of worthwhile to spend the cash to repair it – which Heathrow has beforehand mentioned would have price a billion kilos.

NESO mentioned having three connections to the grid meant there have been “opportunities” to enhance Heathrow’s resilience of provide.

4. National Grid did not know the way vital the substation was

National Grid and the vitality provider SSEN knew that electrical energy from North Hyde went to Heathrow Airport.

But they didn’t know that Heathrow must shut down if that provide was interrupted.

Perhaps if that they had, they might have taken a unique method to upkeep.

Energy suppliers don’t at present know if their clients are counted as “critical national infrastructure (CNI)” – sectors resembling transport, defence, authorities or communications.

The report calls higher communications between CNI operators and their vitality suppliers to make sure that provides don’t get interrupted.

5. Heathrow shouldn’t be completely satisfied

Heathrow got here below a variety of criticism after the hearth – together with the revelation that the chief government Thomas Woldbye was asleep in mattress when the choice was taken to shut the airport.

NESO mentioned its report was not written to “apportion blame”, however Heathrow says it’s now contemplating authorized motion in opposition to National Grid.

In its view the report described “clear and repeated failings” which “could and should” have prevented the hearth.

It mentioned it anticipated National Grid to “take responsibility for those failings.”

National Grid mentioned it had a complete upkeep programme, and would co-operate carefully with the Ofgem investigation.